ZONE CONTROL VALVE SET

Description

Zone Control Valve is a combined unit of signal butterfly valve, water flow indicator, pressure gauge and test & drain valve assembled on fire protection pipeline network of sprinkler system. Zone Check Valves are obligatory used in the sprinkler system. It separates an area into small distribution zone for indication and control the fire moreover for maintenance.

Variants

UL ASSEMBLE MODEL

STANDARD MODEL

BUTTERFLY VALVE

WATER FLOW SWITCH

TEST AND DRAIN VALVE

E0141-80

EN0141-80

3’’ (80mm)

3’’ (80mm)

1’’ (25mm)

E0141-100

EN0141-100

4’’(100mm)

4’’(100mm)

1’’ (25mm)

E0141-150

EN0141-150

6’’(150mm)

6’’(150mm)

2’’(50mm`)

ASSEMBLE ACCESSORIES

BUTTERFLY VALVE

WATER FLOW SWITCH

TEST AND DRAIN VALVE

PRESSURE GAUGE

Image

Image

Image

Image

Approval: UL Listed/Standard  

Standard: UL 1091

Size: NPS 2″ to 8″

Connection: Full lug/ wafer type/ grooved

Working pressure: 175psi (12bar)

Approval: UL Listed/Standard  

Standard: ANSI/ UL 346 

Type: Vane type           Size: NPS 2″ to 8″ 

Flow sensitivity range:    4-10 USGPM for signal   

Maximum surge: 18 FPS (5.5m/s)

Approval: UL Listed/Standard  

Standard: UL Subject 258 

Size: NPS 1″ to 2″ 

Connection: Threaded/ grooved

Working pressure: 300psi (21bar)

Approval: UL Listed/Standard  

Standard: UL 393 

Connection: 1/4″ NPT

 Dial diameter: 3.5″ (90mm) 

Full scale value: 300psi (21bar)         

Working pressure: Max 225psi (16bar)

 